Name: | Description: | Size: | Format: | |
---|---|---|---|---|
837.64 KB | Adobe PDF |
Advisor(s)
Abstract(s)
This study presents a new scheme for power transformers protection, which is based on the analysis of the harmonic content of the differential current Park's vector modulus. The proposed method is able to detect turn-to-turn winding insulation failures, and to distinguish them from magnetising inrush current transients. Experimental and simulation results are presented and discussed.
Description
Keywords
Citation
Oliveira, L.M.R.; Cardoso, A.J.M.Extended Park's vector approach-based differential protection of three-phase power transformers, IET Electric Power Applications, 6, 8, 463-472, 2012.
Publisher
IET - Institution of Engineering and Technology