Study of Airflow around Occupants Seated in Desks Equipped with Upper and Lower Air Terminal Devices for Slightly Warm Environments

dc.contributor.authorConceição, E. Z. E.
dc.contributor.authorRosa, S. P.
dc.contributor.authorCustodio, A. L. V.
dc.contributor.authorAndrade, R. L.
dc.contributor.authorMeira, M. J. P. A.
dc.contributor.authorLucio, M. M. J. R.
dc.date.accessioned2016-01-27T10:33:58Z
dc.date.available2016-01-27T10:33:58Z
dc.date.issued2010
dc.description.abstractThis paper will discuss' the study of turbulent and mean airflow exiting air terminal devices and surrounding occupants sewed in classroom desks for slightly warm environments equipped with personalized ventilation systems with upper and lower air terminal devices. In the turbulent airflow analysis the air root mean square. the air turbulence intensity, and the air velocity fluctuations,frequencies are calculated, while in the mean airflow analysis the mean air velocity and temperature, the human body skin temperature, and the thermal comfort indexes are evaluated using a multi-node thermal regulation model for two different airflow rates. In the experimental tests made in a wood chamber a manikin, a ventilated desk, and two interior climate analyzers are used. The fluctuations of air velocity and temperature are measured in the air terminal devices and in 15 human body sections around the manikin, while the mean value of air relative humidity and mean radiant temperature are evaluated inside the experimental chamber. The mean air temperature in the air terminal devices is around 28 degrees C (82.4 degrees F), while the mean radiant temperature in the occupation area, the mean air temperature far from the occupation area, and the internal mean air relative humidity in the occupation area are around 28 degrees C (82.4 degrees F), 28 degrees C (82.4 degrees F), and 50%, respectively. The airflow rate in tests I and II are 25.75 m(3)/h (15.16 ft(3)/min) and 48.04 m(3)/h (28.27 ft(3)/min), respectively. The mean air velocity, root mean square, and turbulence intensity for test I are 0.59 m/s (1.94 ft/s), 0.13 m/s (0.43 ft/s), and 22.4%, in the upper air terminal device, and 0.9 m/s (2.96 ft/s), 0.15 m/s (0.49 ft/s), and 16.7%, in the lower air terminal device; while, for test II they are 1.72 m/s (5.64 ft/s), 0.16 m/s (0.52 ft/s), and 9.4%, in the upper air terminal device, and 1.06 m/s (3.48 ft/s), 0.16 m/s (0.52 ft/s and 14.9%, in the lower air terminal device. In test I the mean air velocity and the airflow rate are higher in the lower exit air terminal device than in the upper exit air terminal device; while in test II, the opposite is true. It is also true that the skin temperature is slightly lower in test II than in test I, mainly in human body sections near the air terminal devices, such as the chest, arms, and legs. The occupant in test I conditions is thermally uncomfortable; however, in test II conditions, the obtained results are near the comfort recommendations.
dc.identifier.doihttps://dx.doi.org/10.1080/10789669.2010.10390912
dc.identifier.issn1078-9669
dc.identifier.otherAUT: ECO01058;
dc.identifier.urihttp://hdl.handle.net/10400.1/7510
dc.language.isoeng
dc.peerreviewedyes
dc.publisherTaylor & Francis: STM, Behavioural Science and Public Health Titles
dc.relation.isbasedonP-003-58F
dc.titleStudy of Airflow around Occupants Seated in Desks Equipped with Upper and Lower Air Terminal Devices for Slightly Warm Environments
dc.typejournal article
dspace.entity.typePublication
oaire.citation.endPage412
oaire.citation.startPage401
oaire.citation.titleHVAC&R Research
oaire.citation.volume16
person.familyNameConceição
person.givenNameEusébio
person.identifier.ciencia-id6317-FB21-9671
person.identifier.orcid0000-0001-5963-2107
person.identifier.ridI-7931-2015
person.identifier.scopus-author-id6603299150
rcaap.rightsrestrictedAccess
rcaap.typearticle
relation.isAuthorOfPublicationbd0b4c3b-bd28-4e29-ab0b-1ac167828d7f
relation.isAuthorOfPublication.latestForDiscoverybd0b4c3b-bd28-4e29-ab0b-1ac167828d7f

Files

Original bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
Study of Airflow around Occupants.pdf
Size:
3.18 MB
Format:
Adobe Portable Document Format